Strona 1 - USER’S MANUAL

NXL HVAC & COMPACT USER’S MANUAL

Strona 2

10(96) EU Directive HoneywellHoneywellHoneywellHoneywell 2 All NX frequency converters fulfil all EMC immunity requirements (standards EN 61000-6

Strona 3

EU Directive 11(96) 2 EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj

Strona 4

12(96) EU Directive HoneywellHoneywellHoneywellHoneywell 2 EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj Manufacturer&apo

Strona 5

Receipt of delivery 13(96) 3 3. RECEIPT OF DELIVERY NXL frequency converters have undergone scrupulo

Strona 6

14(96) Receipt of delivery HoneywellHoneywellHoneywellHoneywell 3 3.2 Type designation code NXL HVAC HVAC03C2Enclosure & EMC classification2

Strona 7 - 1. SAFETY

Receipt of delivery 15(96) 3 3.5 Warranty Only manufacturing defects are covered by the warranty. The m

Strona 8 - HOT SURFACE

16(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4. TECHNICAL DATA 4.1 Introduction Honeywell NXL is a compact frequency converter wi

Strona 9 - 2. EU DIRECTIVE

Technical data 17(96) 4 Figure 4-1. NXL block diagram

Strona 10

18(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4.2 Power ratings 4.2.1 NXL Compact – Mains voltage 208 – 240 V & 380 – 500 V

Strona 11 - EU DECLARATION OF CONFORMITY

Technical data 19(96) 4 4.2.1 NXL HVAC – Mains voltage 380 – 500 V Mains voltage 380-500 V, 50/60 Hz,

Strona 12

AT LEAST THE 11 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEAS

Strona 13 - 3. RECEIPT OF DELIVERY

20(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4.3 Technical data Input voltage Uin 380 - 500V, -15%...+10% 3~ 208…240V, -15%...+10

Strona 14

Technical data 21(96) 4 Immunity Complies with EN50082-1, -2, EN61800-3 EMC Emissions MF2-MF3: EMC l

Strona 15

22(96) Installation HoneywellHoneywellHoneywellHoneywell 5 5. INSTALLATION 5.1 Mounting 5.1.1 NXL Compact (MF2 and MF3) There are two possible p

Strona 16 - 4. TECHNICAL DATA

Installation 23(96) 5 Figure 5-3. NXL Compact dimensions, MF2 Table 5-1. Dimensions of NXL, MF2

Strona 17

24(96) Installation HoneywellHoneywellHoneywellHoneywell 5 Figure 5-4. NXL Compact dimensions, MF3 W1 W2 W3 H1 H2 H3 H4 H5 H6 H7 D1 D

Strona 18 - EMC-level N

Installation 25(96) 5 5.1.2 NXL HVAC (MF4 – MF6) The frequency converter shall be fixed with fou

Strona 19

26(96) Installation HoneywellHoneywellHoneywellHoneywell 5 CANK5_2DBAB 5.2 Cooling Forced air flow cooling is used for NXL HVAC and NXL Compact s

Strona 20

Installation 27(96) 5 5.3 Changing EMC protection class from H/C to T in NXL HVAC The EMC protect

Strona 21

28(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6. CABLING AND CONNECTIONS 6.1 Power connections Figure 6-1. Power connect

Strona 22 - 5. INSTALLATION

HoneywellHoneywellHoneywell Cabling and connections 29(96) 6 6.1.1 Cabling Use cables with heat resistance of at least +70°C. The cables and th

Strona 23

CONTENTS NXL HVAC & COMPACT USER’S MANUAL INDEX 1 SAFETY 2 EU DIRECTIVE 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 INSTALLATION 6 CABLIN

Strona 24 - Honeywell

30(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.1.1 Cable and fuse sizes Terminal cable size (min/max) Frame Type I

Strona 25

Cabling and connections 31(96) 6 6.1.2 Mounting of cable accessories Enclosed to your NXL frequency converter you have received a plastic bag c

Strona 26

32(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 5. Place the rubber grommets in the openings as shown in Figure 5. 6. Fix

Strona 27

Cabling and connections 33(96) 6 6.1.3 Installation instructions 1 Before starting the installation, check that none of the components of the

Strona 28 - L1 L2 L3

34(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.3.1 Stripping lengths of motor and mains cables Figure 6-5.Stripping of

Strona 29

Cabling and connections 35(96) 6 6.1.3.2 Installation of cables to NXL Note: In case you want to connect an external brake resistor (MF3 and b

Strona 30

36(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-8. NXL Compact, MF3 Figure 6-9. Cable installation in NXL Compact

Strona 31

Cabling and connections 37(96) 6 Installation of an external RFI filter to NXL Compact (MF2-3) The EMC protection class of NXL Compact frequenc

Strona 32

38(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 RFI Filter type Input voltage Dimensions WxHxD (mm) NXLRFIV35 380-500V 3~

Strona 33

Cabling and connections 39(96) 6 Figure 6-13. NXL HVAC (03-12), MF4 Figure 6-14. Cable installation in NXL HVAC (03-12), MF4 Earth terminals

Strona 34 - MAINS MOTOR

ABOUT THE NXL HVAC & COMPACT USER'S MANUAL AND NXL APPLICATION MANUALS Congratulations for choosing the Smooth Control provided by NXL freq

Strona 35

40(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-15. NXL HVAC (16-31), MF5 Figure 6-16. Cable installation in NXL

Strona 36

Cabling and connections 41(96) 6 Figure 6-17. NXL HVAC (38-61), MF6 Figure 6-18. Cable installation in NXL HVAC (38-61), MF6 Brake resistor

Strona 37

42(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.4 Cable installation and the UL standards To meet the UL (Underwriters

Strona 38 - WxHxD (mm)

Cabling and connections 43(96) 6 6.2 Control unit 6.2.1 NXL Compact (MF2 – MF3) The control unit of the NXL frequency converter is integrated

Strona 39 - DC terminals

44(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.3 Control connections The basic control connections are shown below. T

Strona 40

Cabling and connections 45(96) 6 6.2.4 Control I/O Terminal Signal Description 1 +10Vref Reference output Voltage for potentiometer, et

Strona 41

46(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.5 Control terminal signals Terminal Signal Technical information 1 +1

Strona 42 - MF6 4 35

Cabling and connections 47(96) 6 6.2.5.1 Jumper selections on NXL basic board The user is able to customise the functions of the frequency con

Strona 43 - Slot D: Fieldbus boards

48(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-23. Jumper selection for NXL HVAC, MF4 – MF6 !!!!WARNING Check th

Strona 44 - 21 22 23

Cabling and connections 49(96) 6 Figure 6-24. The location of jumper blocks in MF2 (left) and MF3 (right) Figure 6-25. The location of jumper

Strona 45 - Can be programmed as DIN4

HoneywellHoneywellHoneywellHoneywell Index 5(96) NXL HVAC & COMPACT User's Manual Index Date: 28.

Strona 46

50(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.6 Motor thermistor (PTC) connection There are three possibilities to con

Strona 47

Control Keypad 51(96) 7 7. CONTROL KEYPAD The control keypad is the link between the NXL frequency converter and the user. The NXL control keypad f

Strona 48

52(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.1.2 Control place indications The symbols I/O term, Keypad and Bus/Comm (see chap

Strona 49 - Jumper block X7

Control Keypad 53(96) 7 7.2 Keypad push-buttons The NXL seven-segment control keypad features 7 push-buttons that are used for the control of the f

Strona 50 - GND (terminal 11)

54(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 = Start button. Pressing this button starts the motor if the keypad is the act

Strona 51 - 7. CONTROL KEYPAD

Control Keypad 55(96) 7 7.4 Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used

Strona 52

56(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Figure 7-4. Keypad navigation chart STOPREADYI/O termenterenterresetenterSTOPI/O

Strona 53

Control Keypad 57(96) 7 Menu functions Code Menu Min Max Selections M1 Monitoring menu V1.1 V1.24 See chapter 7.4.1 for the monitoring values

Strona 54 - START-UP WIZARD

58(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.1 Monitoring menu (M1) You can enter the Monitoring menu from the Main menu by

Strona 55 - Location

Control Keypad 59(96) 7 Code Signal name Unit ID Description V1.1 Output frequency Hz 1 Frequency to the motor V1.2 Frequency reference H

Strona 56 - No editing!

6(96) Index 6.2.5 Control terminal signals... 46 6.

Strona 57 - Menu functions

60(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.2 Parameter menu (P2) Parameters are the way of conveying the commands of the u

Strona 58 - Figure 7-5. Monitoring menu

Control Keypad 61(96) 7 Figure 7-6. Parameter value change procedure enterSTOPI/O termREADYSTOPI/O termREADYSTOPI/O termREADYSTOPI/O termREADYS

Strona 59

62(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.3 Keypad control menu (K3) In the Keypad Controls Menu, you can choose the cont

Strona 60

Control Keypad 63(96) 7 7.4.3.2 Keypad reference The keypad reference submenu (R3.2) displays and allows the operator to edit the frequency refere

Strona 61 - Control Keypad 61(96)

64(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.4 Active faults menu (F4) The Active faults menu can be entered from the Main m

Strona 62 - Fieldbus

Control Keypad 65(96) 7 7.4.5 Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed fault

Strona 63

66(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 17 Motor underload/ Pump Dry detection/ Broken belt Detection Motor underload protec

Strona 64 - Table 7-3. Fault types

Control Keypad 67(96) 7 53 Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken Check installation. If

Strona 65

68(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.7 System menu (S6) The System menu can be entered from the main menu by pushing

Strona 66

Control Keypad 69(96) 7 T6.8.2.4 Operating hours trip counter hh:mm: ss P6.8.2.5 Clear operating time counter 0 = No action 1 = Clea

Strona 67 - Push Enter to reset!

HoneywellHoneywellHoneywell Safety 7(96) 1 1. SAFETY 1.1 Warnings 1 The components of the p

Strona 68

70(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.7.1 Copy parameters The Copy parameters submenu (S6.3) is located under the Sys

Strona 69 - Control Keypad 69(96)

Control Keypad 71(96) 7 Figure 7-11. Parameter locking 7.4.7.3 Keypad settings In the submenu S6.6 under the System menu you can further customise

Strona 70 - Parameter lock (P6.5.2)

72(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Timeout time (P6.6.3) The Timeout time setting defines the time, after which the key

Strona 71 - Default page (P6.6.1)

Control Keypad 73(96) 7 HMI acknowledge timeout (P6.7.3) This function allows the user to change the timeout of the HMI acknowledgement time. Note!

Strona 72 - Fan control (P6.7.2)

74(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Counters submenu (S6.8.1) In the Counters submenu (S6.8.1) you can find information r

Strona 73

Control Keypad 75(96) 7 Software info submenu (S6.8.3) The following information can be found under the Software info submenu (S6.8.3): Page Conte

Strona 74

76(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 For more information on the expander board-related parameters, see Chapter 7.4.9. Fig

Strona 75

Control Keypad 77(96) 7 7.4.8 Modbus interface NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance wit

Strona 76

78(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.8.2 Termination Resistor The RS-485 bus is terminated with 120 Ω termination

Strona 77

Control Keypad 79(96) 7 Status Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 - - - - - - - - F Z AREF W FLT DIR RUN RDY

Strona 78

8(96) Safety HoneywellHoneywellHoneywellHoneywell 1 1.3 Earthing and earth fault protection The Honeywell NXL frequency converter must always be

Strona 79

80(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.8.5 Fieldbus parameters RS-485 communication status (I6.10.1) With this functio

Strona 80

Control Keypad 81(96) 7 Communication time-out (P6.10.7) If communication between two messages is broken for a longer time than that defined by this

Strona 81

82(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 8. COMMISSIONING 8.1 Safety Before commissioning, note the following directions and war

Strona 82

Commission

Strona 83

84(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 9 Run the start-up tests without the motor being connected to the process, if possible.

Strona 84

Commission

Strona 85 - Table 8-1. Monitoring values

86(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 8.3.2 HVAC parameters in NXL HVAC (Control keypad: Menu P2  B2.1) Code Parameter

Strona 86

Commission

Strona 87

88(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 P2.1.16 P2.1.15.16 Analogue output function 0 12 1 307 0=Not used 1=Output freq. (0

Strona 88 - 9. FAULT TRACING

Fault tracing 89(96) 9 fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault hi

Strona 89

EU Directive 9(96) 2 2. EU DIRECTIVE 2.1 CE marking The CE marking on the product guarantees

Strona 90

90(96) Fault tracing HoneywellHoneywellHoneywellHoneywell 9 17 Motor underload/ Pump Dry detection/ Broken belt Detection Motor underload protect

Strona 91 - Fault tracing 91(96)

Fault tracing 91(96) 9 53 Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken Check installation. If i

Strona 92

92(96) HoneywellHoneywellHoneywellHoneywell 10 10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA Description: I/O expander board with one relay

Strona 93

Expander board NXLOPTAI 93(96) 11 11. DESCRIPTION OF EXPANDER BOARD NXLOPTAI Description: I/O expander board with one relay output (NO), thre

Strona 94

94(96) Expander board NXLOPTAI HoneHoneHoneHoneywellywellywellywell 11 Terminal Parameter setting Description X4 12 +24V Control voltag

Strona 95

NXL HVAC Basic speed control – Quick setup 95(96) 12 12. NXL HVAC BASIC SPEED CONTROL – QUICK SETUP This chapter provides basic setup instructions